A food department is kept at 2128C by a refrigerator in an environment at 308C. The total heat gain to the food department is estimated to be 3300 kJ/h and the heat rejection in the condenser is 4800 kJ/h. Determine the power input to the compressor, in kW and the COP of the refrigerator.

Respuesta :

Answer:

2.2

Explanation:

[tex]Q_u[/tex] = Heat rejection in the condenser = 3300 kJ/h

[tex]Q_L[/tex] = Heat gain to the food department = 4800 kJ/h

Power output is given by

[tex]W=Q_u-Q_L\\\Rightarrow W=4800-3300\\\Rightarrow W=1500\ kJ/h[/tex]

COP of a refrigerator is given by

[tex]COP=\frac{Desired\ effect}{Work}\\\Rightarrow COP=\frac{Q_L}{W}\\\Rightarrow COP=\frac{3300}{1500}\\\Rightarrow COP=2.2[/tex]

The COP of the refrigerator is 2.2